Reset to factory settings

Aus Gude Systems GmbH
Zur Navigation springen Zur Suche springen

Sprache wählen/
Select language:

How can the device be reset to factory settings?

Using the Select/OK button (cold start)

  1. During the cold start, hold down the Select button until the Status LED flashes once every second
  2. The device is now in BootLoader mode
  3. Release theSelect button
  4. Press the select button and hold it down for approx. 6 seconds until the status LED flashes at roughly twice the speed. (An LED display will now show fab)
  5. Release the “'select”' button
  6. Wait until the status LED returns to flashing more slowly once per second
  7. The device has now been reset to factory settings
  8. Switch the device off and on again


Via the select button (1 button/switch)

  1. Press and hold the button for 3 seconds until the status LED flashes in a pattern of one long on, one short off
  2. On a device with a display, the following message appears: "Press again to jump to FIRMWARE"
  3. Wait a further 3 seconds. The status LED will flash in a pattern of two short flashes followed by one long flash
  4. On a device with a display, the message “Press again to FABSETTINGS” will appear -> press the button once briefly
  5. The device is now reset to factory settings (if you wait for 6 seconds instead, the device will return to its initial state)
  6. During the reset, the status LED flashes rapidly -> wait until the status LED returns to flashing slowly (approx. 5 seconds)


Via the select/ok button (warm start)

  1. During operation, press and hold both the select and ok buttons simultaneously until the status LED flashes once per second
  2. The device is now in BootLoader mode
  3. Release the select and ok buttons
  4. Press the select button and hold it down for approx. 6 seconds until the status LED flashes at roughly twice the speed. (The LED display now shows fab)
  5. Release the select button
  6. Wait until the status LED returns to flashing more slowly once per second
  7. The device has now been reset to factory settings
  8. Press and hold both the “select” and ok buttons simultaneously again until the status LED stops flashing
  9. The firmware will now start


Via the web interface

  1. Open the web interface in your browser
  2. Go to Maintenance
  3. Under Restart/Fab Settings, select Restore Fab Settings and Restart Device
  4. A confirmation box will appear – click Yes
  5. The device will restart automatically